UNIVERSITY OF MICHIGAN INDUSTRY PROGRAM OF THE COLLEGE OF ENGINEERING AIR CONDITIONING AS A FACTOR IN ATTAINING HIGH RATES OF INDUSTRIAL PRODUCTION: PERSONNEL EFFICIENCY by James J. B. Worth September, 1957 IP-240

ABSTRACT The effects of high temperature and humidity on work efficiency was first investigated in the late nineteen twenties. Results very strongly indicated that temperature and humidity above a critical point would reduce both mental and physical efficiency. A few companies that have tried plant-wide air conditioning and reported the results of their changes indicate a 10 to 25 percent increase in productivity.

AIR CONDITIONING AS A FACTOR IN ATTAINING HIGH RATES OF INDUSTRIAL PRODUCTION: PERSONNEL EFFICIENCY Definitions The physiological effects of air conditioning have been discussed in an earlier seminar paper but it is the writer's opinion that a brief review of some of the pertinent facts would be advantageous. Effective temperature is a term used quite frequently in the literature and it essentially is nothing more than an arbitrary index which combines into a single value the effect of temperature, humidity and air movement on the sensation of warmth or cold felt by the human body. The numerical scale value is that of the temperature of still, saturated air which would induce an identical sensation. Metabolism, by means of its simplest definition, is the obtaining of energy from the food supply and is measured by heat produced within the body by the process of oxidation. The fundamental thermodynamic process concerned with heat interchanges between the body and its environment is best described by the following equation: M + S, + E + R + C M=+S+E+R+C where M = rate of metabolism and is always positive, S = rate of storage and is plus or minus depending upon whether heat is being stored or depleted owing to a rise or fall in body temperature, E = rate of evaporative heat loss and normally this is positive as the dew point of the air is below body temperature, R rate of radiative heat loss or gain, and is positive when the body surface temperature is above that of the surrounding walls or ambient air, and C = rate of convective heat loss or gain, and its sign is determined in the above description outlined for radiation. 1

Brief Review of Physiological Facts The temperature of the deep tissues of the human body is said to be 98.4~F in normal conditions. It is generally stated that a rise of body temperature to 107~F is likely to be fatal, but there is no equally definite range of fall of temperature which can be regarded as fatal. Heat is continually being generated within the body, even during sleep, as a result of the chemical processes associated with breathing, digestion and physical effort (metabolism). The heat is conducted to the skin partly by the normal conducting power of the body tissues, partly by the bloodstream, and is dissipated from the skin to the environment. Heat cannot be conducted to the skin unless the temperature of the skin is lower than that of the deeper tissues of the body. Observations show that the skin temperature varies over different parts of the body, being lowest of all, over the feet and next lowest over the hands. When the body is cooled at too rapid a rate the following reactions occur: (1) the skin temperature falls, (2) there is an onset of shivering, an involuntary effort to increase the internal production of heat by muscular action, (3) the adrenal and thyroid glands discharge fluids which accelerate the metabolic generation of heat. When the body is cooled at an insufficient rate the sweat glands discharge sweat onto the surface of the skin, where it evaporates and in so doing takes heat from the body. Heat is dissipated from the skin by radiation, convection and. by evaporation [4]. General Remarks The influence of atmospheric conditions in factories and shops upon the health and well-being of the occupants cannot be overlooked. The industrial, worker spends the major part of his active life in an environment where heat, moisture, and in some special cases, injurious elements are constantly evolved by the process of manufacture. These conditions, as a result of their effect on the health and comfort of the workers, are to some extent responsible for the quantity and quality of output and, therefore, for the general efficiency of the plant. There are several references in the literature to laboratory tests involving temperature and humidity and their resultant effect on work level efficiency. Unfortunately the examples of industrial production usage of controlled climate are not as readily available. The Industrial Fatigue Board of England, in a report of its extensive investigation on the fatigue and efficiency of industrial workers, states that for temperatures under 40~F the hourly output was 10 percent above 2

normal. Conversely, a rise in temperature was followed by a decrease in efficiency, and for an external temperature of 65 ~F the hourly output was 10 percent below normal. In a report of the importance of temperature and humidity to physical work the New York State Commissioon Ventilation states that men perform 28 percent less physical work in a temperature of 860F with 80 percent humidity than in one of 680F and 50 percent relative humidity. An estimate of the daily loss in output in an average size industrial plant operating at an efficiency of 70 percent will reveal the financial loss resulting from failure to control the temperature and humidity conditions [71. Experience of air conditioning in many countries has shown that it may be accepted that with relative humidities of 40-70 percent men doing light work indoors can do so with maximum comfort in air temperatures above 60~F, and below 76~F. The optimum actually prescribed will vary in different countries, according to the clothing worn, the degree of physical activity, the average conditions out of doors and the type of heating and ventilation used. It is agreed that very high and very low degrees of relative humidity are to be avoided -- high values because they lead to a feeling of oppression and low values as they eventually produce restlessness and irritability. The differences in what are regarded as the optimum conditions in different countries may be illustrated by a comparison of the recommendations for indoor air conditioning made in England and in the United States. With medium relative humidity the summer optimum is 66~F in England and 76~F in the United States; the winter optimum is 62-64~F in England and 72~F in the United States [31. Test Chamber Experiments Yaglou and McConnell experimented with subjects doing measureable amounts of work at a constant rate in still and in moving air of various temperatures and humidities. Half of the subjects worked in one chamber at still air and the other half worked in another chamber maintained at the same temperature and humidity as the first, but with an air velocity of 350 feet per minute. The work performed consisted in raising a known weight attached to a rope, the latter passing over a pulley and provided with a suitable handle at the other end. The weights were so adjusted that a force of 40 pounds was required to overcome friction of rope and weight guides, and raise the weight at a uniform rate. The distance through which the 3

weights were raised was fixed to 5 feet, so that each pull represented 200 feet lbs of work done. Each subject was required to raise the weight 75 times in 5 minutes. He then rested for the next 5 minutes, and repeated the work alternately thereafter until compelled to leave the chamber either because of fatigue or because of the severity of exposure. At the lower temperatures the subjects were not required to remain in the test chamber longer than 3 hours. The results of the test are summarized in Figure 1 [6]. 200 180 0 o o.~I 0 H rd k a) 0 H) 0-, 0 E-i 160 140 120 100 80 60.... Work in still air --- Work in moving air 20 1 i 1 90 100 110 120 130 140 150 Dry Bulb Temp. Figure 1 In another controlled experiment by Eichna, a series of tests were conducted on garrison-trained soldiers marching at the rate of 3 mph around a track of 77 foot diameter and carrying a 20 lb pack. The conditions of temperature and humidity were carefully controlled, and regular meteorological observations were made during the test. The wall temperatures were approximately the same as the air temperature, though at air 4

temperatures of 120~F it was thought to be 7-9~F lower than the air temperature. The environments in which tests were made were divided into three categories: 1. Easy environments, in which the men completed four hours marching without complaint. 2. Difficult environments, in which the men completed four hours marching but with many complaints and with much, much effort, and had to be urged to continue. 3. Impossible environments in which the group of men as a unit never did more than one hour of marching, and the men had to be goaded to maintain their working rate. About one third of the men lasted out two hours and usually only two or three men finished four hours of marching. Undesirable symptoms developed after 30 minutes, and progressed rapidly. F0zl 0 0 EH P. la 1 120 Dry Bulb Temp. (OF) --- Impossible Work Difficult Work Figure 2 [91 _ - -- Easy Work Figure 2 shows the lines giving a close fit to the conditions of the trials which fell into three categories. The outstanding feature of this diagram is the narrow range of wet-bulb temperature in which the 5

transition from easy to impossible takes place. Thus in saturated air, 92~F was classed as an "easy" environment, 94~F as "difficult" and 96~F as "impossible" [5]. It is a matter of common experience that one's inclination for mental effort may diminish in very hot environments. Mackworth carried out experiments to test this hypothesis. He studied the performance of eleven physically fit wireless telegraphy operators. Before the main tests the men were acclimatized by exposure to effective temperatures of from 87.50-950F for 3 hours a day 5 or 6 days a week over a period of 7-11 weeks. On the test days work was done for 3 hours, during which period nine messages each of 250 groups were transmitted at a speed.of 22 words per minute. The air velocity was 100 feet per minute throughout the tests, and the dry bulb temperature ranged between 85~F and 105~F, with the wetbulb temperature in each instance 10~ below the dry bulb. Theee conditions represented effective temperatures of from 79~ to 97~. Hot and moist atmosphere seriously impaired the accuracy with which these trained men could record the Morse messages. The average numbers of errors per subject per hour are shown in the following table. Average Number of Mistakes Per Hour Dry Bulb (~F) 85 90 95 100 105 Wet Bulb (~F) 75 80 85 90 95 Effective Temperature 79 83 88 92 97 Mistakes per subject per hour 12.0 11.5 15.3 17.3 94.7 The reduction in accuracy when the effective temperature reached 88~F was statistically significant. The data given above are the averages for all the subjects. It is noteworthy that the exceptionally competent members of this group were less affected by the difficult atmospheric conditions than men regarded as very good operators, while men of ordinary ability showed the greatest deterioration of all. This is an interesting point because industrial fatigue studies indicate that under difficult conditions the more competent workers show less signs of fatigue than their fellow workers. There were no signs of cumulative effects from day to day, but during a 3 hour period the number of errors per hour rose progressively. 6

On the whole, errors were twice as numerous in the second hour as in the first, and three times as numerous in the third hour [1]. The New York State Commission on Ventilation conducted controlled chamber tests to evaluate the effects of various stimulus on physical work performed. Groups of subjects were kept in the experimental chamber under four different conditions: 68~F with a fresh-air supply of 45 cfm per person; 68~F with stagnant air; 75~F with the fresh air fans on; and 75~F with stagnant air. In all cases relative humidity was between 49 and 54 percent. For two work periods of one hour, each of the subjects lifted a 5 pound iron dumbell through a distance of 2-1/4 feet as many times as he chose, with no urging from the observer, but with a small additional incentive bonus on the basis of the amount of work performed, as recorded by an automatic counter. Thus a modest piece-work incentive was supplied. The results, for four subjects over a period of 20 days were as follows: Cool Temp. Cool Temp. Warm Temp. Warm Temp. Plus Air Stag. Air Plus Air Stag. Air Ft lbs work 26,711 24,359 22,771 20,481 The maximum figure of 26,711 ft lbs was reduced 9 percent in the cool stagnant air, 15 percent in the warm air with air movement, and 23 percent in the warm stagnant air. It is a striking fact that an increase in air temperature from 68~F to 75~F plus elimination of air movement should cut production down by nearly one quarter (even with moderately low relative humidity) [8]. Experiments and Analysis of Tests with Production Personnel Unfortunately there is very little information in the literature regarding the use of air conditioning in production areas of industrial organizations. Vernon showed a definite need for such considerations in his analysis of the seasonal trend in efficiency for the tin plate rolling mills in England. The analysis showed in heavy work) especially when it involves exposure to high temperature, output undergoes a consistent seasonal variation. It is generally greatest in winter, least in summer and intermediate between the two in spring and autumn. The variations in output noted by these observers are shown in the following table: 7

Relative Output Dec.- Spring- JuneOperations Mar. Autumn Sept. Men charging blast furnaces 105.0 106.5 88.5 Open hearth steel melters-Works C 107.7 102.0 92.2 Open hearth steel melters-Works D 85.7 85.1 84.8 Open hearth steel melters-Works F 102.5 100.5 97.2 Open hearth steel melters-Works J 102.5 104.6 102.8 Rolling mill men 3 107.0 106.5 107.0 Rolling mill men 5 124.0 118.0 111.0 Rolling mill men 6 105.2 98.4 96.5 Men puddling wrought iron 104.7 102.2 96.0 Tinplate mill men 103.3 99.9 96.9 Glass bottle making 101.7 99.6 98.7 Vernon showed the close relationship between the external temperature and the output from tinplate rolling mills. When the relative rate of output was plotted on the same diagram as the mean monthly temperatures, with the latter being shown on a reversed scale, the two curves were found to follow practically the same course. The output in August was about 10 percent less than that in December and January. In factories devoted to hot industry, ventilation is of much importance. Copious supplies of cool air reduces the temperature, and the beneficial, effect of this lowered temperature is enhanced by the additional air movement. Vernon found that in the best ventilated factories the output in summer was only 3 percent less than in winter, while in the worst ventilated factory it was over 13 percent less. Vernon further estimated that in the worst ventilated factory the output on the hottest days was probably 30 percent less than in the coldest weather. An industrial investigation of working efficiency in the mining industry was conducted by Vernon, Bedford and Warner. As an index of the rate of working the time taken to fill a tram with coal was measured, and the amount of time taken in short rests noted. From these data is is possible to calculate approximately the relative efficiency of men working in different places. The dry-bulb temperature observed varied from 63~ to 89~F and the wet-bulb temperature ranged from 59~ to 82~F. In the hotter working places the time taken for resting and the time required to load a tram of coal both increased, and it was calculated that the working efficiency of the men in the hottest places was only 59 percent of that of the men working in the coolest places [1]. 8

T'oday there are several organizations that have their production personnel in air. conditioned. plants but very little specific information is available as to their improved working efficiency. However, the Reynolds Metals Company in Phoenix, Arizona has forwarded information concerning their plant-wide ventilating and cooling system. The Reynolds Phoenix plant operation consists of melting, casting, extruding, heat treating, finishing, and drawing aluminum alloys into a multitude of different sections. The plant consists of approximately 1,500,000 square feet of floor area and is air conditioned with 34 Carrier air washers of various sizes. The washers recirculate 25,300 gallons per minute of spray water while moving 2,500,000 cubic feet of air per minute. The air washing results in a cooling effect equivalent to about 5,600 tons of refrigeration. The installed cooling capacity of the units will handle 123 percent of the plant's internal load and will do an adequate job of cooling at a reasonable cost, so long as the humidity remains fairly low. An estimate of the work efficiency is difficult to determine in. that the plant has never operated in the summer without using the cooling system. The Chief Engineer for the Phoenix plant estimates that without the use of the ventilating and cooling system the overall efficiency would drop 25 percent and that the quality of the finished product would also undoubtedly suffer [10]. Considerations in Evaluating Work Efficiency It was originally assumed that there is a characteristic diurnal curve representing the course of efficiency during the waking hours for the average person. However, this isn't the true situation. To determine a diurnal efficiency curve we must consider the age of the sibjects, their occupation and their own habits, particularly with reference to times of sleeping,eating and peak loads of work demanded by the requirements of their jobs. For example, in school children and adults who perform mental work there is a low point at the beginning of the day, a rise until noon, a slump around mealtime, then a rise in the afternoon followed by a drop in the late evening. On the other hand, tests of physical strength, speed of movement and the like show a steadily increasing efficiency throughout the day into late afternoon, then a subsequent drop. The weekly trends in efficiency are determined by the habits of the particular culture to which a person belongs. Thus we find one type of efficiency curve for the Russian workmen who have no Sunday holiday and whose week differs in length from ours, and an entirely different 9

curve for American workmen. The weekly English industrial curve commences at a low level on Monday9 rises during Tuesday and Wednesday, reaches a peak at midweek, then drops sharply Thursday and recovers partially during Friday and Saturday. Weather conditions are found to have an influence on people's moods and in turn their efficiency. Atmospheric conditions, primarily barometric pressure, also effect efficiency. When the barometer rises, nervousness and irritability increase and ability to concentrate declines [2 ]. The two classic examples of evaluating work efficiency are the early experiments with lighting and sound dampening. Improved lighting was put into a General Electric plant and production went up 25 percent. The lighting was reduced back to its original level and production stayed at its new high. The lighting was further reduced below its original intensity and yet production still remained at its high level. The same situation happened with a computing company in New England. The company proposed reducing the noise level in its computer office and installed sound dampening materials. Production and work efficiency immediately improved. Unfortunately someone in the organization suggested an experiment to put board panels over the sound dampening material. The result was that the noise level hit a new high in the office but efficiency still remained at its new high point. Both of these cases are examples of personnel reaction to management interest in their comfort and well being and not an indication of improved efficiency due to physical changes in the work atmosphere. Conclus ions The aforementioned section on the evaluation of work efficiency is by no means an implication that air conditioning has not improved work efficiency. The author is definitely convinced that air conditioning has and. can improve working efficiency. The only question i.s, how much improvement can be attributed directly to the air conditioning and. what percent is due to miscellaneous other causes and effects. However, the breakdown, of the improved efficiency is an academic question and is of little concern to the industrial organization whose production costs have been reduced and the work efficiency set at a new high. 10

Bibliography 1. Bedford, Thomas, Basic Principles of Ventilation and Heating, London: H. K. Lewis and Company Ltd., 1948, 401 pp. 2. Bills, Arthur Gilbert, The Psychology of Efficiency, New York: Harper and Brothers Publishers, 1943, 361 pp. 3. Brunt, David, "Climate, Weather, and Man," Endeavor,Vol. III, No. 11 ( July, 1.944.) 4. Brunt, David, "Climate and Human Comfort," Proceedings of Royal Institution of Great Britain, Vol. 33, No. 151 (March, 1945). 5. Eichna, L. W., Ashe, W. F., Bean, W. B., and Shelley, W. B., Journal of Industrial Hygiene, Vol. 27, 1945, p. 59. 6. McConnell, W. J., and Yaglou, C. P., Transactions American Society Heating and Ventilating Engineers, Vol. 31, 1925, p. 101. 7. Yaglou, C. P.,, and Miller, W. E., Transactions American Society Heating and. Ventilating Engineers, Vol. 30, 1924, p. 339. 8. Winslow, C. E. A., and Herrington, L. P., Temperature and Human Lif.e, Princeton: Princeton University Press, 1949, 271 pp. Unpublished Material 9. Brunt, David, "The Effect of Humidity on Working Efficiency," A special University of London lecture given at The Royal School of Mines on 7th May, 1946. 10. Gettig, A. D., "Ventilating and Cooling System of the Phoenix Plant," A business reply from the Chief Engineer for the Phoenix Plant of the Reynolds Metals Company, April 5, 1957. 11